  • Model
    SSB-21-6
    SSB-21-10
    SSB21-18
    SSB-21-32
  • Nominal current range, A
    3-6
    5-10
    9-18
    16-32
  • Electric motor nominal rating powers (at voltage 400 V)
    1,1; 1,5; 2,2
    2,2; 3; 4
    4; 5,5; 7,5
    7,5; 11; 15
  • Power part nominal operating voltage
    110..440 V at 50/60 Hz
  • Device power nominal voltage, V
    110..440 AC / 110..565 DC
  • Device maximum power consumption, W
    10
  • Number of adjustable phases
    2
  • Speedup/brake time range, sec.
    1 to 15
  • Initial voltage level, % Uн
    20...90
  • Start current limit range, % Iн
    150...500
  • Underload current level, % Iн
    20...80
  • Operating time at U = 0.8Uн, sec.
    0; 0,2; 0,5; 1
  • Integrated power unit output voltage, V
    24 DC ± 10%
  • Integrated power unit maximum output current, mА
    100
  • Analogue output (active and entire load current monitoring)
    0...10 V, 4...20 mА, 0...20 mА
  • Load hump resistance of analogue output in current mode, Ohm
    500
  • Load minimum resistance of analogue output in potential mode, Ohm
    500
  • Insulated logic inputs voltage of, V
    12...250 AC/12...310 DC
  • Isolated logic AC/DC inputs current, mА
    3
  • Digital outputs maximum voltage, V
    250 AC / 30 DC
  • Digital outputs maximum current, А
    3 AC / 3 DC
  • Overload protection index according to IEC 60947-4-2
    10А, 10, 20, 30
  • Dimensional specifications at vertical installation, H×W×D, mm
    200×95×95
  • Net weight, kg
    1,3
  • Operating temperature range, °С
    -10 to +40
  • Protection level
    IP20
  • Control and protection implementation
    Digital, microcontroller
  • Mode switching
    DIP - switch
  • Parameter setting
    Potentiometers
Device operation mode
Start with voltage ramp. In this mode, the starting device forms a linear stator voltage trajectory, which leads to a smooth change of starting current and starting torque values. This enables to minimize the impact of motor start-up on power network by means of decreasing current leaps and supply voltage interruption.
Start with hump current limit. This is an effective starting mode of induction motor, where the set current value in the whole speedup interval is maintained automatically, which ensures a fault-free start even in the conditions of limited network power.
Soft stop and dynamic break. The soft starter ensures breaking by voltage ramp, dynamic break – by direct current or coasting.
Inching start mode. It is designed for overcoming the initial frictional moment at starting from zero speed. The start is implemented with short (split seconds) circuit voltage supply to motor coils, following which a smooth speedup mode starts. Such mode is completely safe for power network.
Motor protection. The soft starters SSB-21 protect the motor and the mechanism from the impact of such negative effects as: over-current, extended overloads, emergency dry run, inverter overheat, as well as the issues with power supply or rotor lock.
Production and Delivery
  • The soft starters is supplied from our warehouse in Ukraine.
  • If the required models are not available, they can be delivered upon request.
  • If the customer has any specific requirement for the equipment, control units can be produced upon the request.
Technical Support
  • Qualified experts are available to provide consultation on application, installation, setting and exploitation.
  • The selection of technical options according to your needs.
  • Design of automation systems with equipment.

© 2010–2020

"Diada Group" LLC

E-mail: sales.eu@diadagroup.com

Office:

04011, Slovakia, Kosice, Popradská 66

Tel: +421 950 871 307; +421 902 898 157

Manufacture:

03057, Ukraine, Kyiv, 3, Oleksandra Dovzhenko Street, 2nd floor

Tel: +38 (044) 392-06-05, +38 (044) 229-06-06